Model | Smartpack R |
Part number | 242100.120 |
INPUT DATA |
Voltage (nominal) | 10 - 75 VDC |
Power Consumption | 3 W (display sleep, no dist. CAN Power, LVD activation, no USB
power) |
25 W (display on, dist CAN Power, LVD activation, USB Power) |
SYSTEM CONNECTIONS - SYSTEM | |
MONITORS |
Voltage sense, system voltage support | 12 VDC, 24VDC, 48VDC & 60VDC |
Current sense, shunt support | 0 - 20mV, 0-50mV, 0 - 60mV and 0-100mV |
Battery fuse monitoring | Auxiliary switch NO/NC, Pull up/down |
Load fuse monitoring | Auxiliary switch NO/NC, Diode Matrix Pull up/down |
Battery temperature monitoring | AD590 sensor input |
Battery symmetry monitoring (built in) | 4 x Analog Voltage[0-75V] inputs (12, 24 or 60V blocks) |
SYSTEM CONNECTIONS - LVD | |
CONTROL |
Battery disconnect | 1 (latched or non-latched supported) |
Load disconnect | 2 (latched or non-latched supported) |
GENERIC INPUTS AND OUTPUTS |
Digital configurations, Inputs #1-6 | Auxiliary switch: NO/NC |
Analog configurations, Inputs #1-2 | Analog Voltage[0-75V] (Configure as NO, NC, Diode Matrix sense or
Voltage sense) |
Analog configurations, Inputs #3-6 | Analog Voltage[0-75V] (Configure as NO, NC, Diode Matrix sense or
Voltage sense) Support: |
Temperature sense w/ NTC probe |
Output configurations, Outputs #1-6 | 6x Relay–Dry/Form C - Configurable Normally Open/Closed [Max
capacity 75V/2A/60W] |
CONTROL SYSTEM CONNECTIONS |
CAN Power | Distributed CAN Power available +/- 500mA |
CAN Nodes | Support: I/O Monitors, Battery String Monitor, Load/Current
Monitor, Fleximonitor, AC Mains Monitor |
& Smartnode (legacy) |
USER INTERFACE |
Local | Alphanumeric LCD display (Chinese Traditional and Simplified
supported) & 3 keys |
Ethernet port | 10/100 BASE-T (optional: 1000 BASE-T) IPv4/v6 |
(eth 0: LAN port) | IP protocols: HTTP (HTML5 Responsive User Interface) / SSL(TLS w/
self-signed certificate |
(eth 1: Craft port w/DHCP, USB Device | generator or load authenticated certificates), SNMP v3 w/Generic
MIBs & Enterprise MIB type: SP2- |
port) | MIB (Eltek Branch 10), MODBUS TCP and pComm UDP (PowerSuite), VPN,
VLAN, NTP, SFTP &RADIUS |
USB Host
USB Device | Flash Drive for SWFW upgrade and XML configuration file loading |
Config read from Smartpack 1 Gen USB Device port |
wlan0: WiFi dongle for wireless craft port, wwan0: 4G USB Cellular
Modem |
eth2: Ethernet Gigabit |
PC – pComm – Windows PowerSuite |
Serial ports | RS-232 and RS-485 on RJ11 connector |
Serial protocols: MODBUS RTU Slave, MODBUS RTU/ASCII Master
(several pre-defined types and |
full generic configurable data reader available), Modem
Call-Back/SMS reporting (PSTN or GSM) |
and pComm (PowerSuite) |
GENERAL SPECIFICATIONS |
Dimensions (WxHxD) | 109 x 44 (1U) x 156 mm (4.3 x 1.75 x 6.1”) [Chassis dept: 140 mm] |
Temperature Range | Operating -20 to +65˚C (-40 to 149˚F) |
DESIGN STANDARDS |
Electrical safety | UL 60950-1, 2ed, 2014-10-14, EN 60950-1:2006/A2:2013 |
EMC | ETSI EN 300 386 V.2.1.1, EN 61000-6-1(2007) /-2(2005) /-3(2012)
/-4(2011), |
FCC CFR47 Part 15B section 109: 2010 |
Environment | ETSI EN 300 019: 2-1 v2.3.1 (Class 1.2), 2-2 v2.4.1 (Class 2.3) &
2-3 v2.4.1 (Class 3.2) |
2011/65/EU (RoHS) & 2012/19/EU (WEEE) |
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2.
Other operating conditions as per IEC 62040- |
5-3:2016 clause 4.3, must be advised |
> | | |
>